Standard Day Tank with Open 150% Top Containment Basin
UTRS Series 2 GPM supply pump
Tank and Control Description:
Tramont UTRS RB Series diesel fuel tank is a steel rectangular tank with an open top fuel containment basin. Tramont System 2000Plus is an Electronic Control Module (ECM) featuring a microprocessor-based fuel level control and monitoring system. The ECM supervises all performance parameters of the day tank.
UL and National Standards:
Tramont UTRS Series dual wall day tanks are constructed in accordance with the following standards:
-
Underwriters Laboratories Inc.
-
Tank Standard – UL 142 Steel Aboveground Tanks for Flammable and Combustible Liquids (UL Listed under File MH13710)• ECM Standard
-
UL 508 Industrial Control Equipment (UL Listed under File E116902)
-
NFPA 30 – Flammable and Combustible Liquids Code
-
NFPA 37 – Standard for Installation and use of Stationary Combustible Engine and Gas Turbines
-
NFPA 110 – Standard for Emergency and Standby Power Systems
Construction:
Tank is pressurized at 3 psi and leak checked to ensure integrity of weld seams per UL 142 standards prior to shipment. Tanks are constructed of heavy gauge steel. The tank design has been tested extensively under conditions far in excess of normal use. The open top 150% containment basin is leak checked through the application of zyglow to the interior of the containment tank.
In addition, tanks are pressure washed with an iron phosphate solution and then finished with an acrylic primer and gray enamel paint (additional colors available). Tank interior is coated with a solvent-based rust preventative.
Standard Tramont UTRS Series day tanks feature:
-
Emergency pressure relief vent cap – Insure adequate venting and pressure relief inner tank under extreme temperature and emergency conditions.
-
Atmospheric vent cap accommodates normal venting – Accommodates normal venting (oversized 2” vent)
-
Leak detection switch – Top mounted, annunciates a contained fuel leak at ECM control panel
-
2 GPM supply pump with 1/3 HP, 115 VAC, 60 Hz thermally protected motor
System 2000+ Electronic Control Module – Control or Fuel Level Condition |
Signal Contacts¹ or |
Color-coded |
| 106% of capacity High Fuel | Contact (optional) | Red |
| 100% of capacity Full (Tank Full) | N/A | Green |
| 95% of capacity | N/A | Green |
| 90% of capacity |
N/A | Green |
| 87% of capacity primary pump starts |
Power | Green |
| 85% of capacity |
N/A | Green |
| 75% of capacity |
N/A | Yellow |
| Low fuel (62% of capacity) |
Signal N/A | Red |
| 50% of capacity |
N/A | Yellow |
| 25% of capacity |
N/A | Yellow |
| 10% of capacity |
N/A | Yellow |
| Critical low fuel level (6% of capacity) |
Signal | Red |
| Empty (0% of capacity) |
N/A | Red |
| Power available |
N/A | Green |
| ECM functional |
Signal | Green |
| Fuel in containment area (from a separate float switch) |
Signal | Red |
| Power “On” latching switch push button |
N/A | N/A |
| Power “Off” latching switch push button |
N/A | N/A |
| Test momentary switch lights all lights and forces pump operation |
N/A | N/A |
| Test (hidden) momentary switch cycles through all relays to test signal contacts | N/A | N/A |
¹Signal contacts rated @ 3 amps at 120 VAC, normally open and normally closed contacts available.
²Power contacts rated for 1/2 hp motor(s), 120 VAC, single phase, 10 amps each, 20 amps full load.
Tank Drawing Number |
Tank Capacity |
Emergency Vent |
Dimensions |
Weight |
List |
|||||||
Liters |
[Gallons] |
Length |
Width |
Height |
||||||||
mm |
[in.] |
mm |
[in.] |
mm |
[in.] |
KG |
[Lbs.] |
|||||
| 127-0490 | 38 | [10] | 2 | 406 | [16] | 914 | [36] | 540 | [21.25] | 62 | [137] | $ 4,152 |
| 127-0495 | 57 | [15] | 2 | 406 | [16] | 914 | [36] | 641 | [25.25] | 73 | [160] | $ 4,251 |
| 127-0500 | 95 | [25] | 2 | 406 | [16] | 914 | [36] | 845 | [33.25] | 93 | [206] | $ 4,346 |
| 127-0505 | 189 | [50] | 2 | 559 | [22] | 914 | [36] | 1022 | [40.25] | 133 | [293] | $ 4,622 |
| 127-0510 | 227 | [60] | 2 | 711 | [28] | 914 | [36] | 1022 | [40.25] | 147 | [325] | $ 5,010 |
| 127-0515 | 284 | [75] | 2 | 711 | [28] | 914 | [36] | 1022 | [40.25] | 181 | [399] | $ 5,136 |
| 127-0520 | 379 | [100] | 3 | 711 | [28] | 914 | [36] | 1353 | [53.25] | 227 | [501] | $ 5,919 |
| 127-0525 | 568 | [150] | 3 | 1016 | [40] | 914 | [36] | 1353 | [53.25] | 274 | [554] | $ 6,870 |
| 127-0530 | 757 | [200] | 3 | 1270 | [50] | 914 | [36] | 1353 | [53.25] | 341 | [650] | $ 7,803 |
| 127-0535 | 1041 | [275] | 4 | 1778 | [70] | 914 | [36] | 1353 | [53.25] | 486 | [840] | $ 9,294 |
| 127-0540 | 1136 | [300] | 4 | 1143 | [45] | 1219 | [48] | 1505 | [59.25] | 361 | [795] | $ 10,377 |
| 127-0545 | 1325 | [350] | 4 | 1295 | [51] | 1219 | [48] | 1505 | [59.25] | 453 | [999] | $ 10,997 |
| 127-0550 | 1514 | [400] | 4 | 1524 | [60] | 1219 | [48] | 1505 | [59.25] | 509 | [1123] | $ 10,427 |
| 127-0555 | 1703 | [450] | 4 | 1676 | [66] | 1219 | [48] | 1505 | [59.25] | 547 | [1205] | $ 11,257 |
| 127-0560 | 1893 | [500] | 4 | 1854 | [73] | 1219 | [48] | 1505 | [59.25] | 590 | [1300] | $ 12,092 |
| 127-0565 | 2082 | [550] | 4 | 2007 | [79] | 1219 | [48] | 1505 | [59.25] | 696 | [1535] | $ 12,620 |
| 127-0570 | 2271 | [600] | 5 | 2184 | [86] | 1219 | [48] | 1505 | [59.25] | 745 | [1642] | $ 11,766 |
| 127-0575 | 2650 | [700] | 5 | 2134 | [84] | 1524 | [60] | 1505 | [59.25] | 816 | [1800] | $ 13,071 |
| 127-0580 | 3028 | [800] | 5 | 2438 | [96] | 1524 | [60] | 1505 | [59.25] | 903 | [1991] | $ 14,422 |
| 127-0585 | 3407 | [900] | 5 | 2743 | [108] | 1524 | [60] | 1505 | [59.25] | 990 | [2182] | $ 15,809 |
| 127-0590 | 3785 | [1000] | 5 | 3048 | [120] | 1524 | [60] | 1505 | [59.25] | 1076 | [2373] | $ 17,184 |
| Option | ||||||||||||
| No. | Description | List Price | ||||||||||
| 3250 | Critical High Level, Emergency Shutdown | $ 331.20 | ||||||||||
| 1920¹ | Automatic Duplex System 2000Plus Controller; Includes second 2 GPM pump with 1/3 HP, 115 VAC, 60 Hz motor, pump running indicator LED and two check valves. Automatically alternates each pump/motor into lead starting position. | $1,575.60 | ||||||||||
| 1050 | 4 GPM pump and 1/3 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $1270.00 | ||||||||||
| 1055 | 7 GPM pump and 1/3 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $1650.00 | ||||||||||
| 1060 | 7 GPM pump and 1/2 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $1,715.00 | ||||||||||
| 2230 | Fuel strainer, 3/4" NPT, 23 GPM, 100 mesh ("Y" strainer) | $141.60 | ||||||||||
| 2650² | Solenoid valve 1/2" NPT, 4 GPM maximum fuel flow, 120 VAC, normally closed | $406.80 | ||||||||||
| 2652² | Solenoid valve 3/4" NPT, 10 GPM maximum fuel flow, 120 VAC, normally closed | $540.20 | ||||||||||
| ¹For increased pump capacity select 2 qty. pump options listed above. Cover included only when tank uses standard 2 GPM pump and motor. | ||||||||||||
| ²Solenoid valves are designed for installation on pump inlet to prevent tank flooding. Specify voltage if solenoid valve will be actuated by customer's controls. A 100 mesh strainer is required to prevent contamination of The valve and to ensure proper closure. Two solenoid valves are required for duplex pumping systems. | ||||||||||||
Standard Day Tank with Open 150% Top Containment Basin
UTRS Series 2 GPM supply pump and 4 GPM reverse pump, includes AC solenoid valve and fuel strainer
Tank and Control Description:
Tramont UTRS RB Series diesel fuel tank is a steel rectangular tank with an open top fuel containment basin. Tramont System 2000Plus is an Electronic Control Module (ECM) featuring a microprocessor-based fuel level control and monitoring system. The ECM supervises all performance parameters of the day tank.
UL and National Standards:
Tramont UTRS Series dual wall day tanks are constructed in accordance with the following standards:
-
Underwriters Laboratories Inc.
-
Tank Standard – UL 142 Steel Aboveground Tanks for Flammable and Combustible Liquids (UL Listed under File MH13710)
-
ECM Standard – UL 508 Industrial Control Equipment (UL Listed under File E116902)
-
NFPA 30 – Flammable and Combustible Liquids Code
-
NFPA 37 – Standard for Installation and use of Stationary Combustible Engine and Gas Turbines
-
NFPA 110 – Standard for Emergency and Standby Power Systems
Construction:
Tank is pressurized at 3 psi and leak checked to ensure integrity of weld seams per UL 142 standards prior to shipment. Tanks are constructed of heavy gauge steel. The tank design has been tested extensively under conditions far in excess of normal use. The open top 150% containment basin is leak checked through the application of zyglow to the interior of the containment tank.
In addition, tanks are pressure washed with an iron phosphate solution and then finished with an acrylic primer and gray enamel paint (additional colors available). Tank interior is coated with a solvent-based rust preventative.
Standard Tramont UTRS Series day tanks feature:
-
Emergency pressure relief vent cap – Insures adequate venting and pressure relief inner tank under extreme temperature and emergency conditions.
-
Atmospheric vent cap accommodates normal venting – Accommodates normal venting (oversized 2” vent)
-
Leak detection switch – Top mounted, annunciates a contained fuel leak at ECM control panel
-
2 GPM supply pump and 4 GPM reverse pump each with 1/3 HP, 115 VAC, 60 Hz thermally protected motor
-
Electric solenoid valve with 100 mesh fuel strainer – maintains prime in return (reverse) fuel line to main tank
System 2000+ Electronic Control Module – Control or Fuel Level Condition |
Signal Contacts¹ or |
Color-coded |
| 106% of capacity High Fuel |
Contact (optional) | Red |
| 100% of capacity Full (Tank Full) |
N/A | Green |
| 95% of capacity |
N/A | Green |
| 90% of capacity |
N/A | Green |
| 87% of capacity primary pump starts |
Power | Green |
| 85% of capacity |
N/A | Green |
| 75% of capacity |
N/A | Yellow |
| Low fuel (62% of capacity) Signal |
N/A | Red |
| 50% of capacity |
N/A | Yellow |
| 25% of capacity |
N/A | Yellow |
| 10% of capacity |
N/A | Yellow |
| Critical low fuel level (6% of capacity) |
Signal | Red |
| Empty (0% of capacity) |
N/A | Red |
| Power available |
N/A | Green |
| ECM functional |
Signal | Green |
| Fuel in containment area (from a separate float switch) |
Signal | Red |
| Power “On” latching switch push button |
N/A | N/A |
| Power “Off” latching switch push button |
N/A | N/A |
| Test momentary switch lights all lights and forces pump operation |
N/A | N/A |
| Test (hidden) momentary switch cycles through all relays to test signal contacts |
N/A | N/A |
¹Signal contacts rated @ 3 amps at 120 VAC, normally open and normally closed contacts available.
²Power contacts rated for 1/2 hp motor(s), 120 VAC, single phase, 10 amps each, 20 amps full load.
Tank Drawing Number |
Tank Capacity |
Emergency Vent (inches) |
Dimensions |
Weight |
List |
Liters |
[Gallons] |
Length |
Width |
Height |
mm |
[in.] |
mm |
[in.] |
mm |
[in.] |
KG |
[Lbs.] |
| 127-0595 | 38 | [10] | 2 | 406 | [16] | 914 | [36] | 743 | [29.25] | 74 | [163] | $ 7,015 |
| 127-0600 | 57 | [15] | 2 | 406 | [16] | 914 | [36] | 845 | [33.25] | 84 | [186] | $ 7,114 |
| 127-0605 | 95 | [25] | 2 | 406 | [16] | 914 | [36] | 1048 | [41.25] | 105 | [232] | $ 7,208 |
| 127-0610 | 189 | [50] | 2 | 559 | [22] | 914 | [36] | 1226 | [48.25] | 145 | [319] | $ 7,484 |
| 127-0615 | 227 | [60] | 2 | 711 | [28] | 914 | [36] | 1226 | [48.25] | 159 | [351] | $ 7,873 |
| 127-0620 | 284 | [75] | 2 | 711 | [28] | 914 | [36] | 1226 | [48.25] | 193 | [425] | $ 7,998 |
| 127-0625 | 379 | [100] | 3 | 711 | [28] | 914 | [36] | 1556 | [61.25] | 239 | [527] | $ 8,782 |
| 127-0630 | 568 | [150] | 3 | 1016 | [40] | 914 | [36] | 1556 | [61.25] | 286 | [631] | $ 9,732 |
| 127-0635 | 757 | [200] | 3 | 1270 | [50] | 914 | [36] | 1556 | [61.25] | 352 | [777] | $ 10,666 |
| 127-0640 | 1041 | [275] | 4 | 1778 | [70] | 914 | [36] | 1556 | [61.25] | 498 | [1097] | $ 12,157 |
| 127-0645 | 1136 | [300] | 4 | 1143 | [45] | 1219 | [48] | 1708 | [67.25] | 372 | [821] | $ 13,239 |
| 127-0650 | 1325 | [350] | 4 | 1295 | [51] | 1219 | [48] | 1708 | [67.25] | 465 | [1025] | $ 13,859 |
| 127-0655 | 1514 | [400] | 4 | 1524 | [60] | 1219 | [48] | 1708 | [67.25] | 521 | [1149] | $13,003 |
| 127-0660 | 1703 | [450] | 4 | 1676 | [66] | 1219 | [48] | 1708 | [67.25] | 558 | [1231] | $13,833 |
| 127-0665 | 1893 | [500] | 4 | 1854 | [73] | 1219 | [48] | 1708 | [67.25] | 601 | [1326] | $14,669 |
| 127-0670 | 2082 | [550] | 4 | 2007 | [79] | 1219 | [48] | 1708 | [67.25] | 708 | [1561] | $15,197 |
| 127-0675 | 2271 | [600] | 5 | 2184 | [86] | 1219 | [48] | 1708 | [67.25] | 757 | [1668] | $14,055 |
| 127-0680 | 2650 | [700] | 5 | 2134 | [84] | 1524 | [60] | 1708 | [67.25] | 828 | [1826] | $15,361 |
| 127-0685 | 3028 | [800] | 5 | 2438 | [96] | 1524 | [60] | 1708 | [67.25] | 915 | [2017] | $16,712 |
| 127-0690 | 3407 | [900] | 5 | 2743 | [108] | 1524 | [60] | 1708 | [67.25] | 1002 | [2208] | $18,099 |
| 127-0695 | 3785 | [1000] | 5 | 3048 | [120] | 1524 | [60] | 1708 | [67.25] | 1088 | [2399] | $19,474 |
| Option | ||||||||||||
| No. | Description | Pricing | ||||||||||
| 1920¹ | Automatic Duplex System 2000Plus Controller; Includes second 2 GPM pump with 1/3 HP, 115 VAC, 60 Hz motor, pump running indicator LED and two check valves. Automatically alternates each pump/motor into lead starting position. | $ 1,575.60 | ||||||||||
| 1050/1055/2652² | 4 GPM supply pump, 7 GPM reverse pump and solenoid valve 3/4" NPT in lieu of standard 2, 4 GPM pumps and 3/4" solenoid valve. | $ 3460.00 | ||||||||||
| ¹Cover included when tank uses standard 2 GPM pump and motor. | ||||||||||||
| ²Solenoid valves are designed for installation on pump inlet to prevent tank flooding. Specify voltage if solenoid valve will be actuated by customer's controls. A 100 mesh strainer is required to prevent contamination of The valve and to ensure proper closure. Two solenoid valves are required for duplex pumping systems. | ||||||||||||
Weather Protective Day Tank with Containment Basin
UTRS Series 2 GPM supply pump
Tank and Control Description:
Tramont UTRS RB Series diesel fuel tank is a steel rectangular tank with a sealed fuel containment basin. Tramont System 2000Plus is an Electronic Control Module (ECM) featuring a microprocessor-based fuel level control and monitoring system. The ECM supervises all performance parameters of the day tank.
UL and National Standards:
Tramont UTRS Series dual wall day tanks are constructed in accordance with the following standards:
-
Underwriters Laboratories Inc.
-
Tank Standard – UL 142 Steel Aboveground Tanks for Flammable and Combustible Liquids (UL Listed under File MH13710)
-
ECM Standard – UL 508 Industrial Control Equipment (UL Listed under File E116902)
-
NFPA 30 – Flammable and Combustible Liquids Code
-
NFPA 37 – Standard for Installation and use of Stationary Combustible Engine and Gas Turbines
-
NFPA 110 – Standard for Emergency and Standby Power Systems
Construction:
Inner and outer tank is pressurized at 3 psi and leak checked to ensure integrity of weld seams per UL 142 standards prior to shipment. Tanks are constructed of heavy gauge steel. The tank design has been tested extensively under conditions far in excess of normal use. The open top 150% containment basin is leak checked through the application of zyglow to the interior of the containment tank.
In addition, tanks are pressure washed with an iron phosphate solution and then finished with an acrylic primer and gray enamel paint (additional colors available). Tank interior is coated with a solvent-based rust preventative.
Standard Tramont UTRS Series day tanks feature:
-
Emergency pressure relief vent cap – Insure adequate venting and pressure relief inner and outer tank under extreme temperature and emergency conditions.
-
Atmospheric vent cap accommodates normal venting – Accommodates normal venting (oversized 2” vent)
-
Leak detection switch – Top mounted, annunciates a contained fuel leak at ECM control panel
-
2 GPM pump with 1/3 HP, 115 VAC, 60 Hz thermally protected motor
System 2000+ Electronic Control Module – Control or Fuel Level Condition |
Signal Contacts¹ or |
Color-coded |
| 106% of capacity High Fuel |
Contact (optional) | Red |
| 100% of capacity Full (Tank Full) |
N/A | Green |
| 95% of capacity |
N/A | Green |
| 90% of capacity |
N/A | Green |
| 87% of capacity primary pump starts |
Power | Green |
| 85% of capacity |
N/A | Green |
| 75% of capacity |
N/A | Yellow |
| Low fuel (62% of capacity) |
Signal N/A | Red |
| 50% of capacity |
N/A | Yellow |
| 25% of capacity |
N/A | Yellow |
| 10% of capacity |
N/A | Yellow |
| Critical low fuel level (6% of capacity) |
Signal | Red |
| Empty (0% of capacity) |
N/A | Red |
| Power available |
N/A | Green |
| ECM functional |
Signal | Green |
| Fuel in containment area (from a separate float switch) |
Signal | Red |
| Power “On” latching switch push button |
N/A | N/A |
| Power “Off” latching switch push button |
N/A | N/A |
| Test momentary switch lights all lights and forces pump operation |
N/A | N/A |
| Test (hidden) momentary switch cycles through all relays to test signal contacts | N/A | N/A |
¹Signal contacts rated @ 3 amps at 120 VAC, normally open and normally closed contacts available.
²Power contacts rated for 1/2 hp motor(s), 120 VAC, single phase, 10 amps each, 20 amps full load.
Tank Drawing Number |
Tank Capacity |
Emergency Vent (inches) |
Dimensions |
Weight |
List |
Liters |
[Gallons] |
Length |
Width |
Height |
mm |
[in.] |
mm |
[in.] |
mm |
[in.] |
KG |
[Lbs.] |
| 127-0700 | 38 | [10] | 2 | 406 | [16] | 914 | [36] | 540 | [21.25] | 52 | [115] | $ 4,867 |
| 127-0705 | 57 | [15] | 2 | 406 | [16] | 914 | [36] | 641 | [25.25] | 82 | [180] | $ 4,979 |
| 127-0710 | 95 | [25] | 2 | 406 | [16] | 914 | [36] | 845 | [33.25] | 83 | [184] | $ 5,082 |
| 127-0715 | 189 | [50] | 2 | 559 | [22] | 914 | [36] | 1022 | [40.25] | 142 | [313] | $ 5,385 |
| 127-0720 | 227 | [60] | 2 | 711 | [28] | 914 | [36] | 1022 | [40.25] | 156 | [345] | $ 5,830 |
| 127-0725 | 284 | [75] | 2 | 711 | [28] | 914 | [36] | 1022 | [40.25] | 190 | [419] | $ 5,956 |
| 127-0730 | 379 | [100] | 3 | 711 | [28] | 914 | [36] | 1353 | [53.25] | 236 | [521] | $ 6,892 |
| 127-0735 | 568 | [150] | 3 | 1016 | [40] | 914 | [36] | 1353 | [53.25] | 283 | [625] | $ 7,906 |
| 127-0740 | 757 | [200] | 3 | 1270 | [50] | 914 | [36] | 1353 | [53.25] | 350 | [771] | $ 8,951 |
| 127-0745 | 1041 | [275] | 4 | 1778 | [70] | 914 | [36] | 1353 | [53.25] | 495 | [1091] | $ 10,661 |
| 127-0750 | 1136 | [300] | 4 | 1143 | [45] | 1219 | [48] | 1505 | [59.25] | 370 | [815] | $ 11,862 |
| 127-0755 | 1325 | [350] | 4 | 1295 | [51] | 1219 | [48] | 1505 | [59.25] | 462 | [1019] | $ 12,523 |
| 127-0760 | 1514 | [400] | 4 | 1524 | [60] | 1219 | [48] | 1505 | [59.25] | 518 | [1143] | $11,840 |
| 127-0765 | 1703 | [450] | 4 | 1676 | [66] | 1219 | [48] | 1505 | [59.25] | 556 | [1225] | $12,745 |
| 127-0770 | 1893 | [500] | 4 | 1854 | [73] | 1219 | [48] | 1505 | [59.25] | 599 | [1320] | $13,656 |
| 127-0775 | 2082 | [550] | 4 | 2007 | [79] | 1219 | [48] | 1505 | [59.25] | 705 | [1555] | $14,240 |
| 127-0780 | 2271 | [600] | 5 | 2184 | [86] | 1219 | [48] | 1505 | [59.25] | 754 | [1662] | $13,378 |
| 127-0785 | 2650 | [700] | 5 | 2134 | [84] | 1524 | [60] | 1505 | [59.25] | 826 | [1820] | $14,796 |
| 127-0790 | 3028 | [800] | 5 | 2438 | [96] | 1524 | [60] | 1505 | [59.25] | 912 | [2011] | $16,260 |
| 127-0795 | 3407 | [900] | 5 | 2743 | [108] | 1524 | [60] | 1505 | [59.25] | 999 | [2202] | $17,758 |
| 127-0800 | 3785 | [1000] | 5 | 2946 | [116] | 1524 | [60] | 1505 | [59.25] | 1085 | [2393] | $19,246 |
| Option | ||||||||||||
| No. | Description | Pricing | ||||||||||
| 3250 | Critical High Level, Emergency Shutdown | $ 331.20 | ||||||||||
| 1920¹/2410 | Automatic Duplex System 2000Plus Controller; Includes second 2 GPM pump with 1/3 HP, 115 VAC, 60 Hz motor, pump running indicator LED and two check valves. Automatically alternates each pump/motor into lead starting position. WPE cover | $ 2,143.20 | ||||||||||
| 1050 | 4 GPM pump and 1/3 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $ 1,270.00 | ||||||||||
| 1055 | 7 GPM pump and 1/3 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $ 1,650.00 | ||||||||||
| 1060 | 7 GPM pump and 1/2 HP, 115 VAC, 1 phase motor (replaces 2 GPM std. pump) | $ 1,715.00 | ||||||||||
| 2230 | Fuel strainer, 3/4" NPT, 23 GPM, 100 mesh ("Y" strainer) | $ 141.60 | ||||||||||
| 2650² | Solenoid valve 1/2" NPT, 4 GPM maximum fuel flow, 120 VAC, normally closed | $ 406.80 | ||||||||||
| 2652² | Solenoid valve 3/4" NPT, 10 GPM maximum fuel flow, 120 VAC, normally closed | $ 540.00 | ||||||||||
| ¹For increased pump capacity select 2 qty. pump options listed above. Cover included only when tank uses standard 2 GPM pump and motor. | ||||||||||||
| ²Solenoid valves are designed for installation on pump inlet to prevent tank flooding. Specify voltage if solenoid valve will be actuated by customer's controls. A 100 mesh strainer is required to prevent contamination of The valve and to ensure proper closure. Two solenoid valves are required for duplex pumping systems. | ||||||||||||
Weather Protective Day Tank with Containment Basin
UTRS Series 2 GPM supply pump and 4 GPM reverse pump, includes AC solenoid valve and fuel strainer
Tank and Control Description:
Tramont UTRS RB Series diesel fuel tank is a steel rectangular tank with a sealed fuel containment basin. Tramont System 2000Plus is an Electronic Control Module (ECM) featuring a microprocessor-based fuel level control and monitoring system. The ECM supervises all performance parameters of the day tank.
UL and National Standards:
Tramont UTRS Series dual wall day tanks are constructed in accordance with the following standards:
-
Underwriters Laboratories Inc.
-
Tank Standard – UL 142 Steel Aboveground Tanks for Flammable and Combustible Liquids (UL Listed under File MH13710)
-
ECM Standard – UL 508 Industrial Control Equipment (UL Listed under File E116902)
-
NFPA 30 – Flammable and Combustible Liquids Code
-
NFPA 37 – Standard for Installation and use of Stationary Combustible Engine and Gas Turbines
-
NFPA 110 – Standard for Emergency and Standby Power Systems
Construction:
Inner and outer tank is pressurized at 3 psi and leak checked to ensure integrity of weld seams per UL 142 standards prior to shipment. Tanks are constructed of heavy gauge steel. The tank design has been tested extensively under conditions far in excess of normal use. The open top 150% containment basin is leak checked through the application of zyglow to the interior of the containment tank.
In addition, tanks are pressure washed with an iron phosphate solution and then finished with an acrylic primer and gray enamel paint (additional colors available). Tank interior is coated with a solvent-based rust preventative.
Standard Tramont UTRS Series day tanks feature:
-
Emergency pressure relief vent cap – Insures adequate venting and pressure relief inner and outer tank under extreme temperature and emergency conditions.
-
Atmospheric vent cap accommodates normal venting – Accommodates normal venting (oversized 2” vent)
-
Leak detection switch – Top mounted, annunciates a contained fuel leak at ECM control panel
-
2 GPM supply pump and 4 GPM reverse pump each with 1/3 HP, 115 VAC, 60 Hz thermally protected motor
-
Electric solenoid valve with 100 mesh fuel strainer – maintains prime in return (reverse) fuel line to main tank
System 2000+ Electronic Control Module – Control or Fuel Level Condition |
Signal Contacts¹ or |
Color-coded |
| 106% of capacity High Fuel |
Contact (optional) | Red |
| 100% of capacity Full (Tank Full) |
N/A | Green |
| 95% of capacity |
N/A | Green |
| 90% of capacity |
N/A | Green |
| 87% of capacity primary pump starts |
Power | Green |
| 85% of capacity |
N/A | Green |
| 75% of capacity |
N/A | Yellow |
| Low fuel (62% of capacity) |
Signal N/A | Red |
| 50% of capacity |
N/A | Yellow |
| 25% of capacity |
N/A | Yellow |
| 10% of capacity |
N/A | Yellow |
| Critical low fuel level (6% of capacity) |
Signal | Red |
| Empty (0% of capacity) |
N/A | Red |
| Power available |
N/A | Green |
| ECM functional |
Signal | Green |
| Fuel in containment area (from a separate float switch) |
Signal | Red |
| Power “On” latching switch push button |
N/A | N/A |
| Power “Off” latching switch push button |
N/A | N/A |
| Test momentary switch lights all lights and forces pump operation |
N/A | N/A |
| Test (hidden) momentary switch cycles through all relays to test signal contacts | N/A | N/A |
¹Signal contacts rated @ 3 amps at 120 VAC, normally open and normally closed contacts available.
²Power contacts rated for 1/2 hp motor(s), 120 VAC, single phase, 10 amps each, 20 amps full load.
Tank Drawing Number |
Tank Capacity |
Emergency Vent (inches) |
Dimensions |
Weight |
List Pricing |
Liters |
[Gallons] |
Length |
Width |
Height |
mm |
[in.] |
mm |
[in.] |
mm |
[in.] |
KG |
[Lbs.] |
| 127-0805 | 38 | [10] | 2 | 406 | [16] | 914 | [36] | 743 | [29.25] | 83 | [183] | $ 7,927 |
| 127-0810 | 57 | [15] | 2 | 406 | [16] | 914 | [36] | 845 | [33.25] | 93 | [206] | $ 8,039 |
| 127-0815 | 95 | [25] | 2 | 406 | [16] | 914 | [36] | 1048 | [41.25] | 114 | [252] | $ 8,142 |
| 127-0820 | 189 | [50] | 2 | 559 | [22] | 914 | [36] | 1226 | [48.25] | 154 | [339] | $ 8,371 |
| 127-0825 | 227 | [60] | 2 | 711 | [28] | 914 | [36] | 1226 | [48.25] | 168 | [371] | $ 8,817 |
| 127-0830 | 284 | [75] | 2 | 711 | [28] | 914 | [36] | 1226 | [48.25] | 202 | [445] | $ 8,942 |
| 127-0835 | 379 | [100] | 3 | 711 | [28] | 914 | [36] | 1556 | [61.25] | 237 | [527] | $ 9,879 |
| 127-0840 | 568 | [150] | 3 | 1016 | [40] | 914 | [36] | 1556 | [61.25] | 295 | [651] | $ 10,892 |
| 127-0845 | 757 | [200] | 3 | 1270 | [50] | 914 | [36] | 1556 | [61.25] | 362 | [797] | $ 11,938 |
| 127-0850 | 1041 | [275] | 4 | 1778 | [70] | 914 | [36] | 1556 | [61.25] | 507 | [1117] | $ 13,647 |
| 127-0855 | 1136 | [300] | 4 | 1143 | [45] | 1219 | [48] | 1708 | [67.25] | 381 | [841] | $ 14,849 |
| 127-0860 | 1325 | [350] | 4 | 1295 | [51] | 1219 | [48] | 1708 | [67.25] | 474 | [1045] | $ 15,510 |
| 127-0865 | 1514 | [400] | 4 | 1524 | [60] | 1219 | [48] | 1708 | [67.25] | 530 | [1169] | $14,527 |
| 127-0870 | 1703 | [450] | 4 | 1676 | [66] | 1219 | [48] | 1708 | [67.25] | 567 | [1251] | $15,432 |
| 127-0875 | 1893 | [500] | 4 | 1854 | [73] | 1219 | [48] | 1708 | [67.25] | 611 | [1346] | $16,344 |
| 127-0880 | 2082 | [550] | 4 | 2007 | [79] | 1219 | [48] | 1708 | [67.25] | 717 | [1581] | $16,928 |
| 127-0885 | 2271 | [600] | 5 | 2184 | [86] | 1219 | [48] | 1708 | [67.25] | 766 | [1688] | $15,767 |
| 127-0890 | 2650 | [700] | 5 | 2184 | [86] | 1524 | [60] | 1708 | [67.25] | 837 | [1846] | $17,185 |
| 127-0895 | 3028 | [800] | 5 | 2438 | [96] | 1524 | [60] | 1708 | [67.25] | 924 | [2037] | $18,649 |
| 127-0900 | 3407 | [900] | 5 | 2743 | [108] | 1524 | [60] | 1708 | [67.25] | 1011 | [2228] | $20,148 |
| 127-0905 | 3785 | [1000] | 5 | 3048 | [120] | 1524 | [60] | 1708 | [67.25] | 1097 | [2419] | $21,635 |
| Option | ||||||||||||
| No. | Description | Pricing | ||||||||||
| 1920¹/2410 | Automatic Duplex System 2000Plus Controller; Includes second 2 GPM pump with 1/3 HP, 115 VAC, 60 Hz motor, pump running indicator LED and two check valves. Automatically alternates each pump/motor into lead starting position. WPE cover | $ 2,143.20 | ||||||||||
| 1050/1055/2652² | 4 GPM supply pump, 7 GPM reverse pump and solenoid valve 3/4" NPT in lieu of standard 2, 4 GPM pumps and 3/4" solenoid valve. | $ 3,460.00 | ||||||||||
| ¹Cover included only when tank uses standard 2 GPM pump and motor. | ||||||||||||
| ²Solenoid valves are designed for installation on pump inlet to prevent tank flooding. Specify voltage if solenoid valve will be actuated by customer's controls. A 100 mesh strainer is required to prevent contamination of the valve and to ensure proper closure. Two solenoid valves are required for duplex pumping systems. | ||||||||||||
Local Code Approval Options
Option Packages for Day Tanks
Most of the United States uses the guidelines as set forth by the National Fire Protection Agency (NFPA) as the installation standard that governs tank products for flammable and combustible liquids. Some local governments exercise the “Authority Having Jurisdiction” status and have created their own requirements (in addition to NFPA) for installation of flammable and combustible liquid storage tanks.
Tramont Corporation, the nation’s leading designer and manufacturers of UL listed diesel fuel control and UL listed containments systems, supplies more of these systems than anyone in the industry, and is your authority on these national guidelines and local code approvals.
To assist in the specification of your fuel containment system we offer Local Code Approval option packages to ensure your fuel containment system can be specified and be in compliance regardless of its ultimate destination. We have listed examples of some of the local code option packages that satisfy these requirements. If your area is not listed, simply ask your Tramont account representative, your authority on national and local codes.
City of Los Angeles Fire Code
Tramont Corporation approved by the Los Angeles Bureau of Fire Prevention
Option # |
Description |
| 1998 | Los Angeles Bureau of Fire Prevention, day tank Approval No. 12-88-1 |
| 2005 | Manual Fitting and Lockable Fill Cap, 2” NPT (replaces standard fill cap)LAFD Approval Label |
| 2230 |
3/4” NPT, 100 Mesh “Y” Strainer |
| 1710 |
Hand pump rated @20 GPM per 100 strokes |
| 2450 |
Drain Petcock Valve (ship loose) |
| 2650 | 1/2” NPT, 115 VAC, N.C. Solenoid Valve (4gpm maximum) |
Special Note:
Day tank packages with reverse pump include supply line solenoid valve deduct $339
City of Chicago
Tramont Corporation approved by the department of inspectional services–Plan No. 0451
Option # |
Description |
| 1997 | City of Chicago Approval Package, no bottom fittings |
| 3175 | OFF Push Button Disable |
| 2397 | Eliminate all Bottom Tank Fittings |