Tramont Main Tanks
UL 142 Listed Main Supply Tank
A cylindrical main fuel supply tank is the economical approach when a larger fuel capacity is required or as a main fuel tank for a day tank. In addition this can be an excellent "companion fuel tank" to extend the fuel reserve capacity of your generator's sub base fuel tank when used with a Tramont Modular Fuel Transfer System. |
UL 2085 Listed Fireguard Main Tank
The Fireguard tank offers a UL Listed fire rated protected design featuring a unique lightweight thermal insulation that is up to 75% lighter than concrete encased designs - reducing shipment and installation costs. Exterior steel wall provides superior durability and low-cost maintenance. Unlike concrete outer shell versions cracking will never present a problem. |
Standard Features for both UL 142 & UL 2085 Tanks:
- Manual Fuel Fill Cap, 2" flip top cap design allows a customer supplied lock to be added for a secure fuel fill access .
- Fuel Level Gauge, stand-up fuel gauge provides "At-A-Glance" reading of fuel level.
- Leak Detection Gauge, stand-up mechanical provides "At-A-Glance" notification of liquid within the secondary containment tank.
- Removable Supply & Return Dip Tube, Set of quantity 2- 2" removable dip tubes enter through 2" NPT tank fitting.
- 2" Normal Vent (Updraft) with Screen, For atmospheric venting includes pipe riser. Shipped installed.
- 3"-8" Appropriately Sized Emergency Pressure Relief Vent, For emergency venting purposes as prescribed in NFPA 30-2003 4.2.5.2 Shipped installed on tank.
|
| Tank Capacity |
|
Tank Capacity |
|
| Gallons |
Model # |
Thickness |
Emer. Vent |
L (in) |
Dia. (in) |
H (in) |
Weight (lbs) |
Gallons |
Model # |
Thickness |
Emer. Vent |
L (in) |
Dia. (in) |
H (in) |
Weight (lbs) |
| 250 |
N/A |
|
|
|
|
|
|
250 |
1116-11097 |
7 gauge |
3" |
72 |
47 |
54 |
2,100 |
| 560 |
1116-11115 |
12 gauge |
3" |
72 |
48 |
55 |
1,500 |
560 |
1116-11098 |
7 gauge |
4" |
84 |
60 |
67 |
2,600 |
| 1000 |
1116-11116 |
10 gauge |
4" |
72 |
64 |
71 |
2,500 |
1000 |
1116-11099 |
7 gauge |
4" |
78 |
70 |
77 |
5,000 |
| 1000 |
1116-11117 |
10 gauge |
6" |
132 |
48 |
55 |
2,500 |
1000 |
1116-11100 |
7 gauge |
6" |
138 |
54 |
61 |
5,400 |
| 1500 |
1116-11118 |
7 gauge |
6" |
108 |
64 |
71 |
3,000 |
1500 |
1116-11101 |
7 gauge |
6" |
114 |
70 |
77 |
6,600 |
| 2000 |
1116-11119 |
7 gauge |
6" |
144 |
64 |
71 |
4,000 |
2000 |
1116-11102 |
7 gauge |
6" |
150 |
70 |
77 |
8,300 |
| 2500 |
1116-11120 |
7 gauge |
6" |
180 |
64 |
71 |
4,500 |
2500 |
1116-11104 |
7 gauge |
6" |
186 |
70 |
77 |
10,000 |
| 2500 |
1116-11121 |
7 gauge |
6" |
144 |
72 |
79 |
4,500 |
2500 |
1116-11105 |
7 gauge |
6" |
150 |
78 |
85 |
11,000 |
| 3000 |
1116-11122 |
1/4" |
6" |
216 |
64 |
71 |
6,000 |
3000 |
1116-11107 |
1/4" |
6" |
222 |
70 |
77 |
11,000 |
| 4000 |
1116-11123 |
1/4" |
6" |
144 |
96 |
103 |
6,500 |
4000 |
1116-11108 |
1/4" |
6" |
174 |
90 |
97 |
13,600 |
| 5000 |
1116-11124 |
1/4" |
6" |
168 |
96 |
103 |
7,400 |
5000 |
1116-11109 |
1/4" |
6" |
174 |
102 |
110 |
19,000 |
| 6000 |
1116-11125 |
1/4" |
8" |
192 |
96 |
103 |
8,500 |
6000 |
1116-11110 |
1/4" |
8" |
198 |
102 |
110 |
19,500 |
| 8000 |
1116-11126 |
1/4" |
8" |
252 |
96 |
103 |
11,500 |
8000 |
1116-11111 |
1/4" |
8" |
258 |
102 |
110 |
23,500 |
| 10000 |
1116-11127 |
1/4" |
8" |
330 |
96 |
103 |
14,500 |
10000 |
1116-11112 |
1/4" |
8" |
326 |
102 |
110 |
29,000 |
| 12000 |
1116-11128 |
1/4" |
8" |
384 |
96 |
103 |
17,000 |
12000 |
1116-11113 |
1/4" |
8" |
390 |
102 |
110 |
33,000 |
| 15000 |
N/A |
|
|
|
|
|
|
15000 |
1116-11114 |
1/4" |
8" |
414 |
126 |
134 |
39,000 |
Optional Main & Fire-Rated Tank Accessories
Main Tank Options |
| Option Name |
Option # |
Description |
| Transport Fuel Fill/Spill Cabinet |
2500-11129 |
30 gal. overfill cabinet attaches to tank end (head), includes all piping. Attaches to 3" spacers installed during production - adds 25" to overall length; mounting is 36" up from tank bottom. Dimensions 22"L x 18"W x 30"H. Not available as a field retrofit. |
| Transport Fuel Fill/Spill Cabinet |
2500-11130 |
Same as above except includes an Overfill Prevention Valve. |
| Ladder with Arm Rails 3.9 feet |
2500-11131 |
Convenient ladder simplifies access for tank fill & maintenance. Ladder mounts to tank end. Not available as a field retrofit. |
| Ladder with Arm Rails 4.5 feet |
2500-11132 |
Not available as a field retrofit. |
| Ladder with Arm Rails 5.8 feet |
2500-11133 |
Not available as a field retrofit. |
| Ladder with Arm Rails 6.5 feet |
2500-11134 |
Not available as a field retrofit. |
| Ladder with Arm Rails 7.5 feet |
2500-11135 |
Not available as a field retrofit. |
| Ladder with Arm Rails 8.5 feet |
2500-11136 |
Not available as a field retrofit. |
| Ladder with Arm Rails 9.5 feet |
2500-11137 |
Not available as a field retrofit. |
| Ladder with Arm Rails 10.5 feet |
2500-11138 |
Not available as a field retrofit. |
| 24" Manway allows tank access |
2500-11139 |
Manway opening allows entrance into the tank for periodic maintenance, tank cleaning or emergency repair. Recommended for 5000 gallons tanks and larger. |